Northstar Pkwy

New Construction, Site Work

No Information to Display

$2,000,000.00

Public - City

img_map_placeholder

Northstar Pkwy, Fort Worth, TX

Subscribe to View Full Documents

The lift station has been designed for a capacity of 1,600 GPM, with a total dynamic head (TDH) of approximately 310 feet and submersible pumps are the only accepted technology. The motors shall be 75 hp and larger and suitable sections that is within the approval list of pump vendors are KSB, Flygt and Sulzer. The submersible pumps will operate based on wet well levels that will be monitored using a Siemens Multiranger/Hydroranger 100/200 sensor, with floats as a backup. The power and controls for pumps will be housed in a building. SCADA equipment will communicate with a 900 MHz Eagle Mountain Tower. All PLC and SCADA equipment will be fed from a UPS backup power source. Standby power will be provided via a diesel-fueled generator, stand-by rated, sized to run one (1) pump with enough reserve fuel for a minimum of 24 hours as required by 30 TAC 217.63. The proposed pump arrangement will consist of a 1 duty pump plus 2 stand-by pumps, with lead/lag alternation. The second stand-by pump was included as a requirement from the City of Fort Worth operations personnel for redundancy purposes. Motors on the three pumps are estimated to be 235 HP each. proposed wet well is a rectangular cast in place concrete structure with an epoxy lining. For consistent operation during emergency and non-emergency operations, only one pump should run at all times given the force main carrying capacity, therefore the installed controls should completely stop the operating pump before allowing the next pump to start. The controls should be programmed to lock out starting the next pump when one is running on generator/power, to avoid overloads if another pump should try to start. The generator will be enclosed within a soundproof enclosure and be equipped with a network connection to communicate with the station PLC. Variable Frequency Drives (VFD) will be installed for controlled ramp starting and stopping of pump motors. VFDs will be installed in NEMA 12 enclosures inside of a conditioned electrical building, which will be specified at a later stage depending on material lead times. In compliance with 30 TAC 217.59 (d), Odor control will be required A preliminary bid list of Bid Items include; Lift station structure, pipe gallery, pumps, VFDs along with an Electrical building and 12" Force Main approximately 2,590 feet. Typical piping, valves, paving, grading, site work, chain link fence and gate, odor control and Electrical, instrumentation and controls. The Construction plans and Specifications are at 90% Completion at this time, but prior to signing the Contractual Documents, final Engineer's Bid Quantities will be provided to the selected Contractor Each bid must be accompanied by a certified or cashier's check, from a responsible bank in the State of Texas, or a bid bond, issued by a surety legally authorized to do business in the State of Texas, equal to 5% of the total bid amount. Make the cashier's check, certified check or bid bond payable to 170 NORTHSTAR RANCH DEVELOPER, INC. MUNICIPAL UTILITY DISTRICT, (M.U.D.). Developer and City reserves the right to waive irregularities and to accept or reject bids Address questions to: City of Fort Worth 200 Texas Street Fort Worth, TX 76102 Attn: Taylor Gunderman, PE, Development Services - Water Email: taylor.gunderman@fortworthtexas.gov Phone: 682.402.7050

7 Record(s)

Subscribe to Get All Contact Details

Trades

Division 00 - Lorem Ipsum

Division 00 - Lorem Ipsum

Lorem, Ipsum, Dolor, Sit amet
Subscribe to See All Trade Details

You’ve Reached the Free View Limit

Want to see more project and bidder data in your market? Check out our product options and see what works best for you and your business.

Come back in [[refresh_days]] to get [[project_count]] more free projects.